Sheathing Under Standing Seam Steel
Standing seam steel roofing is manufactured from interlocking roll formed steel panels which are crimped, or snapped, together on site. The panels and seams run vertically from the top of the ridge to the eave side of the roof. The panels are fastened to the framework below by means of either clips or screws which allow the panels to flex in length to compensate for expansion and contraction due to temperature change.
Panels are typically 12 to 18 inches in width, with a narrow tall “rib” along each long side of the panel. These steel panels are rarely structural, as far as their ability to span between roof purlins and carry a snow load, so the majority of manufacturers recommend installation over solid sheathing.
Due to the large flat “pan” between the ribs of the standing seam steel, the panels are prone to oil can, or look wavy. Installation over smooth sheathing surfaces, tends to minimize the effects of oil canning.
American Building Components (www.abcmetalroofing.com) recommends their SL Series® roofing panels be applied over a properly aligned, smooth continuous substrate such as 5/8” or thicker plywood with a suitable moisture barrier between.
How about other manufacturers?
Union Corrugating (www.unioncorrugating.com) merely states, “Install the Advantage-Lok II Standing Seam Roof System on solid decking”, without defining what the solid decking is. When researching the Florida NOA (Notice of Acceptance) for the product, it specifies the decking to be either plywood or wood plank.
Fabral (www.fabral.com) also says to install their Ultra Loc, Horizon 16 and Horizon S panels also use the solid decking term.
This “solid decking” thing continued to perplex me, so I found the UL® online certifications directory at www.floridabuilding.org and see the system for all listed manufacturers (most major United States roll formers) requires:
Substructure — (Plywood) — Plywood decking to be a nominal 5/8 in. thick, exposure sheathing span C-D, 40/20 plywood. All butt joints to be sealed against leakage by using tape and/or caulk or with one-part urethane sealant.”
Planning on using a standing seam steel roofing product? I would most strongly recommend it be installed over 5/8” plywood.
Why? Because the screws will stay in the plywood!
DEAR JAVO: Clip lock standing seam panels have no ability to transfer wind shear loads and should only be installed over 5/8″ CDX plywood sheathing. If not, your building is likely to rack (or even fail) due to wind loads. There are other reasons to use sheathing:
DEAR CHAD: Unlike all Hansen Pole Buildings with spans of 40 foot or less (where we have our interior double trusses always designed to be able to support at least a minimal ceiling load of five pounds per square foot), most pole barn trusses are not ordered or designed to support any sort of a ceiling. Many times trusses will have a stamp on them stating truss spacing and loads, if so, you want a Bottom Chord Dead Load of 5 psf or greater. If nothing else, truss manufacturer’s stamp will tell you who fabricated those trusses and you can reach out to them to verify adequacy. If they do not have records available, or are no longer in business, you should engage a Registered Professional Engineer to perform a field inspection to verify adequacy, or to provide an engineered repair.

DEAR GREG: In your climate zone I would typically not recommend using spray foam other than as two inch thickness applied directly to steel roofing and/or siding in order to control condensation. This does result in having to mechanically control humidity as your building will now “dry” to inside. As standing seam steel does not provide shear resistance, it must be installed over solid decking – and you can spray foam directly to this decking underside.
DEAR MIKE: Absolutely do not cut or notch into your end rafter. You need to lower end rafters to allow purlins to go over top of end rafters without any notching.
In most instances, you are better served with sidewall columns spaced every 12 feet. Use a true two-ply truss, aligned with every sidewall column (