Loft in a Weld Up Steel Building

Loft in a Weld Up Steel Building

Reader CINDY in TYLER writes:

“I am constructing the interior of a welded metal house that’s 20x18x12. I am trying to figure out how to add a loft. The building framing is constructed of I-beams and the walls have 2 rows of heavy 8” C-channel per wall, Though the lower C’s will have to be cut for window installation. But the upper C is about the right height for the floor. I only want the loft to be 20×9. I’m going to give you my ideas and would like your response, ideas, thoughts and recommendations please. I have a 20’ piece of steel 8” C-channel that I could run across the building that would finish the square framing, though I don’t weld ad not sure how to best attach it to the walls. After that I can install, with screws, 2×8 along the inside of all the C’s. That will give something to attach joist hangers to which will be installed parallel to the C that was just installed. Does this sound doable and any ideas on how to properly attach the C channel? I was thinking I could cut the top and bottom part that curls, and bend it out of the way and attach some heavy duty angle pieces, but can only attach with 1’s onto the top and bottom of one channel and to the center of another. I would attach with bolts and nuts. Any help will be greatly appreciated. Thank you for all that you do for so many people with your blog.” 

Mike the Pole Barn Guru says:

If you are a regular follower of my blog posts, you will find I am a fan of weld up steel buildings only when they are fabricated from engineer sealed site specific plans with assembly done by a certified welder. While this may not be as important on a low risk shed, as buildings grow in footprint and complexity, it becomes significantly important.

Lofts can prove to be of special concern. They tend to be under designed (unless engineered) and over loaded, resulting in distinct possibilities of catastrophic failure leading to potential injuries (if not fatalities).

Trying to attach steel beams to steel framing members should not be done without an engineer’s design. There is an easier option:

Provided your concrete slab is sufficiently thick, my recommendation would be to frame 2×6 stud walls along each 20 foot side of your proposed loft. Use a pressure preservative treated 2×6 bottom plate. Studs can be 24 inches on center with a double 2×6 top plate.

Proper anchorage for stud wall to a slab has fasteners penetrating at least an inch into concrete. You could use 2-1/2″ Ramset nails.

Personally, I prefer using Tapcon screws 

What you’ll need:

Tapcon screws – Be sure to get 3/16″ x 2-3/4″
ones with hex heads. Don’t try to use a flat-head screwdriver to drive them! 

A hammer drill

Several concrete drill bits

A hex head bit for drill fitting Tapcon head size

How to attach walls using Tapcon screws

Drill pilot hole

Drill a hole through 2×6 bottom plate center, every 16″ to 20″ inches.

Hold the bottom plate in place by standing on it if possible.

Use firm pressure, but don’t push too hard. Save your body, drill will do the work!

If using 2 3/4″ screws, put a piece of tape on bit 3″ from tip. (Drill 1/4″ deeper than depth of anchor plus 1 1/2″ for bottom plate.)

Attach screw

For best results use a hex-head attachment on your power drill to secure screw. (Even the correct size flat-head screwdriver attachment will slip off frequently.)

Start off slowly until you’re through the bottom plate.

Speed up drill and drive anchor deep enough into concrete so the screw head is flush with bottom plate. 

Make sure you have enough drill bits on hand. You’ll go through several as tips eventually wear

Another method of attachment entirely avoids penetrating your concrete – construction out or break off. Repeat this process with each wall section adhesive. Make sure the slab is thoroughly clean and use a polyurethane adhesive. Polyurethane works if there is any moisture in the concrete or bottom plate and it has gap filling properties.

Assuming you will have no loads on loft greater than a 40 psf (pounds per square foot) residential load, 2×8 #2 floor joists can be spaced on top of walls 24 inches on center.                                                                                https://www.southernpine.com/app/uploads/SPtable2_060113.pdf

Use 3/4″ OSB (Oriented Strand Board) or CDX plywood for your floor decking. 

A Hay Barn Challenge

Seemingly every small town in America has one or more pole barn ‘builders’. Many of them are more jack-of-all-trades and masters of none. They frame a few houses, do a deck or two, maybe some interior remodels in winter months and along with this – a handful of pole barns.

Sadly, in my humble opinion, many jurisdictions have minimal (or no) permitting requirements for pole barns. This practice is extended even further when it comes to pole barns deemed to be for agricultural purposes.

Combine lack of structural knowledge (plus pooh pooing any need for an engineer) by ‘builders’ as mentioned above with not needing a permit and situations arise rife with a potential for possible calamity.

Reader KATHY in KIMBALL writes:

“We have a ranch in western Nebraska. There are two hay barns on the ranch, each is 64’x44′ with 20 foot from ground to bottom of trusses. These are constructed with the trusses on 4 foot centers on double top plate and V bracing. The side walls are fully sheeted and the end walls are open. Both hay barns are level and in good shape. However, we were loading hay out of one of the barns recently, with wind gusts north of 40 MPH and we could see the trusses moving slightly with the wind, the bottom of the columns were stable as they are encased in concrete.

My questions are: Would it add significant support to build an end wall on one end of each of these barns. If so, can Hansen provide the materials and tech support to build these end walls?

Is there anything else we can do to add strength and stability to these hay barns?”

Mike the Pole Barn Guru replies:
Post frame (pole) buildings work much like unibody cars and jet aircraft, it is their skin’s strength holding everything together. Here is a home experiment you can do to get a better idea (as well as an extended read): https://www.hansenpolebuildings.com/2011/12/lateral-wind-loads/

Your hay barns happen to be a worst case scenario when it comes to sound structural design of a post frame building: https://www.hansenpolebuildings.com/2018/03/ends-open-pole-barn-challenge/

What these buildings really need is to have both endwalls at least partially (if not fully) enclosed from eave to ground. If this is something you would entertain, we could connect you directly with one of our third-party independent engineers to determine if there is a practical solution to your situation.

Meanwhile, make sure your buildings have good replacement value insurance coverage and avoid being anywhere near them if wind speeds are at or beyond what you have already mentioned as causing your concerns.

Bookshelf Girts or Stud Walls?

Why Use Bookshelf Girts Rather Than Studs?

Long time readers may recall my Grandpa Pete was a home builder and his sons – Sid (my father), Neil, Lyle, Gil, Dave and Amund were all framing contractors. https://www.hansenpolebuildings.com/2011/06/before-the-pole-barn-guru/. Besides being raised with “wood is good”, I had a concept of vertical stud walls permanently ingrained in my head!

Stud walls led to my losing my posterior erecting my first post frame (pole barn) building. I struggled with this 90 degree ‘flip’ in framing concept far more than I needed to. Luckily, I was able to wrap my head around left-to-right rather than up and down when it came to my second building and I actually made some very good money!

Reader TRENT in WALLA WALLA writes:

“I am currently working on plans for building my first post frame home. It will be 30×48 single story. I am trying to figure out the best wall girt design. I am looking at going with 2×8 bookshelf wall girts or vertical stud walls between the posts. I see more people going with bookshelf girts vs vertical studs. Is there any drawbacks or reasons not to use vertical stud wall framing between the posts?”

Mike the Pole Barn Guru responds:

Installing a ceilingPretty straightforward – vertical stud walls will take more lumber. Besides increased material investment, more pieces mean more connections and more labor.

Imagine, if you will, a pole building with a 10′ eave height and columns every 12 feet. Bookshelf girts take (1) 2x4x12′ pressure treated, (4) 2x8x12′, (2) 2x4x8′ for blocking girts ends and (2) 2x4x12′ to attach drywall at the ceiling level – 98.67 board feet of lumber. For stud walls (1) 2x6x12′ pressure treated, (7) 2x6x10′ studs, (1) 2x6x12′ top plate, (1) 2x4x12′ to attach drywall at ceiling level, (4) 2x4x12′ horizontally to attach steel to wall studs – 134 board feet of lumber. From a structural aspect, care will need to be exercised in attachment of the top plate and end studs to adequately transfer wall bay wind loads to columns. It may necessitate some sort of Simpson strap to properly anchor the plate to columns.